GENERAL FEATURES |
|
Unlike HART XL, HART MINI which take and analyze air sample in a volume
of room, Stratos-Micra 25, 100 and Stratos-HSSD
2 allows to design air sampling pipe
and holes at the point near the equipment such as air conditioning, rack
equipment, UPS and Battery. This allows to determine accurate position
may cause early fire. |
-
Ultra small low cost aspirating smoke detector for easy and discreet
installation.
-
High sensitivity provided by
laser based forward light scatter for reliable early warning.
-
Sensitivity adjustable from
0.002%Obs/m to 25%Obs/m.
-
Unique ClassiFire-3D® Perceptive
Artificial Intelligence System.
-
Laser Dust Discrimination (LDD)
with a patented dust management and separator system.
-
RS485 communications built in as
standard for networking up to 127 detector per loop.
-
SenseNET software manages16
loops, up to 2032 detector.
-
Interface with Fire Alarm System,
BMS.
-
Control the fire protection
system such FM-200, NOVEC™1230.
|
|
STRATOS-MICRA 25, 100 AND STRATOS-HSSD 2 |
|
|
|
Single sampling pipe
(D=15 - 25mm) up to 25m in length (moving air) and 50m
in length (still air). Operation status displays on LED. |
 |
|
|
|
|
Single sampling pipe
(D=15 - 25mm) up to 50m in length (moving air) and
100m in length (still air). Operation status displays on
LED. |
 |
|
|
|
|
4 sampling pipes (D=15
- 25mm) up to 250m maximum total length, maximum single
pipe up to 100m in length. Stratos-HSSD 2 has some types:
LED display, LCD display, with command module. |
 |
|
|
|
|
Similar to Stratos-Micra 25
but used in explosion proof environment, meet ATEX ated EExd IIB
+ H2T3. Equipment group 2 (zones 1, 2 and 3). Group Gases A and
B + Hydrogen. |
 |
|
|
|
|
Command module is the
LCD display, control, communication with all
Stratos-Micra 25, 100 and Stratos-HSSD 2 via RS485
network. Each Command Module can manage 127 Stratos,
communicate with SenseNET software, control fire suppression
system, interface with fire alarm and BMS. |

|
|
|
REMOTE DISPLAY
UNIT (RDU)
|
|
|
|
CRDU mimics the status
of Stratos visually. It includes 26 levels of warning: fault,
pre-alarm, Fire 1 alarm, Fire 2 alarm. RDU can connect and
display separately for each Stratos or connect to RS485 network
indicating the entire system. Communicating with software SenseNET. |

|
|
|
SenseNET MANAGEMENT SOFTWARE
|
|
|
|
As
a PC graphics system SenseNET™ is a Windows® based program that
provides central management and monitoring of up to 16 loops,
each of up to 127 Stratos. The SenseNET™ PC interface with
Stratos network by RS485 - RS232 converter or RS485 - TIC/IP
converter for remote control through LAN/WAN/Internet.
Real-time indication of alarms /definable sound files.
Displays maps with specific instructions.
Remote configuration of Stratos detector and entire system.
SiteAudit™ logs all events in real time.
SiteMail™ and SitePage™ for automatic email/text alarm alerts.
|
 |
|
|
SenseNET & MANAGEMENT SOFTWARE |
|
 |